Vsg/R Vacuum Circuit Breaker with Lateral Operating Mechanism

Breaking Capacity: High Voltage Circuit Breakers
Operation: Electric Type
Speed: Normal Type Circuit Breaker
Arc-extinguishing Medium: Vacuum
Installation: Withdrawable
Structure: Vcb
Customization:
Gold Member Since 2013

Suppliers with verified business licenses

Manufacturer/Factory & Trading Company

Basic Info.

Model NO.
VSG/R
Poles Number
3 Pole
Type
Circuit Breaker
Function
Short-Circuit
Certification
ISO9001-2000, CCC
Transport Package
Plywood
Trademark
Talent
Origin
China
HS Code
8535210000
Production Capacity
5000 Pieces/Year

Product Description

VSG/R Vacuum Circuit Breaker with Lateral Operating Mechanism
Description
 VSG/R Vacuum Circuit Breaker with lateral operating mechanism is fixed installation. It is mainly used for fixed switchgear. The circuit breaker can be used alone. It is more suitable for ring network power supply, box transformer or various non-standard  power supply systems.
Parameters

Technical Information
Technical Specification          
Rated voltage KV   12 24
Rated current A   630,1250,1600,2500,3150  
Rated frequency HZ   50 50
Rated insulation level        
           1min power frequency witchstand voltage KV   42/48 65
            Lightning impulse withstand voltage KV   75/85 125
Rated short circuit breaking current KA 20/25   31.5 31.5
4S rated short circuit withstand current  KA 20/25   31.5 31.5
Rated peak tolerable current KA 50/63   80 80
Rated short circuit switching current (peak value) KA 50/63   80 80
Operation sequence of automatic reclosure   O-0.3s-CO-180s-CO  score-0.3s-score-180s-score
Arcing time  ms     ≤15  
Rated short circuit breaking current times 100   50 100
Mechanical life times   20000 20000
Contact opening (according to vacuum tube) mm   11±1(9±1) 13±1
Contact overrun mm   3.5±0.5 3±1
Contact closing bounce time ms   ≤3 ≤2
Different periods of Three-phase closing ms   ≤2 ≤2
Opening speed m/s   0.9~1.5 0.9~1.7
Closing speed m/s   0.5~0.9 0.6~1.0
Opening time ms   ≤50 20~50
Closing time ms   ≤100 35~70
Main circuit resistance          
          Rated current:630A μΩ   ≤50 ≤45
          Rated  current:1250A     ≤40 ≤35
Interphase centre distance mm   210±2 210,270,275

Overall and installation dimensions
Vsg/R Vacuum Circuit Breaker with Lateral Operating Mechanism





 

Send your message to this supplier

*From:
*To:
*Message:

Enter between 20 to 4,000 characters.

This is not what you are looking for? Post a Sourcing Request Now

You Might Also Like

Gold Member Since 2013

Suppliers with verified business licenses

Manufacturer/Factory & Trading Company
Number of Employees
85
Year of Establishment
1996-01-16