Number | Item | Unit | FN12-12Load switch | FZN21-12Vacuum load switch | |||
1 | Rated voltage | KV | 10 | ||||
2 | Maximum working voltage | KV | 12 | ||||
3 | Rated frequency | HZ | 50 | ||||
4 | Rated current | A | 630 | ||||
5 | Rated breaking current | A | 630 | ||||
6 | Rated thermal current (Virtual value) | KA/S | 20/2 | 20/4 | |||
7 | Rated dynamic current | KA | 50 | 50 | |||
8 | Short-circuit current (Peak value) | KA | 50 | 50 | |||
9 | Full-load breaking times | times | 20 | 10000 | |||
10 | Mechanical life | times | 2000 | 10000 | |||
11 | 1-min power frequency withstand voltage (phase to earthing) | KV | 42 | 42 | |||
12 | Lightning impulse withstand voltage(phase to earthing) | KV | 75 | 75 |
Number | Rated voltage (KV) |
Rated current (A) |
Breaking current (KA) |
Fuse rated current (A) |
|
British type | Domestic type | ||||
SDL*J | 12 | 40 | 31.5 | 6.3,10,16,20,25,31.5,40 | |
SFL*J | XRNT-12 | 12 | 100 | 31.5 | 50,63,71,80,100 |
SKL*J | 12 | 125 | 31.5 | 25 |
Type | Release form | Release rated current (A) | Making-breaking capacityKA (AC380V) |
DW15-630 | thermo electromagnetic | 315,400,630 | 40 |
DW15-1000 | electronic form | 630,800,1000 | 50 |
DW15-1600 | 1600 | 50 | |
DW15-2500 | 1600,2000,2500 | 60 | |
CW1-2000 | Intelligent form | 630,800,1000,1250,1600,2000 | 65(80) |
CW1-3200 | 2000,2500,3200 | 100 | |
Note: According to whether install striker or not. N means no, A means yes |
Item | Unit | Parameter | |||
High voltage unit | Rated frequency | HZ | 50 | ||
Rated voltage | KV | 6/10/35 | |||
Maximum working voltage | KV | 6.9/11.5/40.5 | |||
Rated current | A | 400,630,1250 | |||
Transfer current | A | 1200~3150 | |||
power frequency withstand voltage (phase to earthing /Isolating fracture) | KV | 42/48 | |||
Lightning impulse withstand voltage (phase to earthing /Isolating fracture) | KV | 75/85 | |||
Rated short circuit current (current-limiting fuse) | KA | 31.5 | |||
Transformer unit | Rated voltage | KV | 6,10,35 | ||
Rated capacity | KVA | 30~2000 | |||
Tapping range | % | ±2×2.5%, ±5% | |||
Vector group | Yyn0, Dyn11 | ||||
impedance voltage | % | 4,4.5,6,8 | |||
Low voltage unit | Rated voltage | V | 220,380,690,800 | ||
Main loops rated current | A | 50~4000 | |||
Branch current | A | 5~800 | |||
Shell | Protection class (conventional product) | High-voltage chamber IP33/Transformer chamber IP23/ Low- voltage chamber IP33 | |||
Noise level | dB | ≤50 |